FP302
Foundation Fieldbus to Pneumatic Signal
Converter
Clique na tecnologia para baixar manuais, firmwares, certificados e arquivos relacionados:
In order to connect existing valve actuators to a FIELDBUS system, SMAR developed a FIELDBUS to pneumatic signal converter, with very low air consumption and a very stable output signal. A 0 to 100% digital signal from the FIELDBUS is converted into a 3 to 15 psi or 3 to 30 psi pneumatic signal according to a characteristic curve selected by the user. Besides the normal PID control function, linearization, master capability, alarms and damping, the FP302 offers signal limitation and reversing and many other features for valve actuation:
Output signal: 3 to 15 psi (default) or 3 to 30 psi (extended)
Supply pressure: 18 to 100 psi;
Vibrating resistant;
PID Controller
Can be mounted in any position;
Accuracy: 0.4 % of the span.
Some Characteristics:
Communication
Digital only, Foundation Fieldbus, 31.25 kbit/s voltage mode with bus power
Output
3-15 psi (0,2-1,0 kg/cm²) or 3 to 30 psi (0,2-2,1 kg/cm 2)
Output
Capacity
3.40 Nm3/h (2 scfm) @ 1.24 bar (18 psi) air supply;
6.80 Nm3/h (4 scfm) @ 2.8 bar (40 psi) air supply;
15.30 Nm3/h (9 scfm) @ 7 bar (100 psi) air supply.
Accuracy
0.4%
of span
Power
Supply
Bus
powered: 9-32 Vdc
Power
Consumption
Quiescent
12 mA
Function
Blocks
Up
to 20 Dynamically Instantiable Function Blocks.
Click here for the list of available Function
Blocks
The Function Blocks available allow simple and complex control strategies to be placed inside the field device, making the field device an integral part of the control system. In order to fully benefit from the Function Blocks in the device a True Foundation Fieldbus system is recommended. For more
information about SYSTEM302, click here.
Configuration
Using local adjustment magnetic tool if device is fitted with LCD display. Complete configuration possible using PC software interface.
Supply Pressure
18 - 100 psi (1,24 - 7 kg/cm²)
Indication
Optional
LCD indicator
Material
Injected
low copper aluminum with polyester painting or 316 stainless steel
housing
Process
Temperature Limits
-40
to 85ºC (-40 to 185 ºF)
Ambient
Humidity Limits
0
to100 % RH
Hazardous
Area Certification
Check order code.
Mounting
Wall,
panel, or 2" pipe with optional bracket
Weight
Nominal:
1.80 kg;
Digital display adds: 0.13 kg;