SMAR Survey Questions
In an effort to improve our services, please take a minute to send your valuable feedback by answering our survey.
|
|
IF302
Triple Channel Current to FOUNDATIONTM Fieldbus Converter
The IF302 is from the first generation of Fieldbus devices. It is a
converter mainly intended for interface of analog transmitters to a
Fieldbus network. The IF302 receives a current signal, typically 4-20 mA
or 0-20mA, and makes it available to the Fieldbus system. The digital
technology used in the IF302 enables a single model to accept three
inputs and also provide several types of transfer functions, an easy
interface between the field and the control room and several
interesting features that reduce considerably the installation, operation
and maintenance costs.
The IF302 is part of Smar’s complete 302 series of Fieldbus devices. Fieldbus is a complete system
enabling distribution of the control function to equipment in the field.
Using Fieldbus technology, with its capability to interconnect several devices, very large control
schemes can be constructed. In order to be user friendly, the function block concept was
introduced. The user may now easily build and overview complex control strategies. Another
advantage is added flexibility, the control strategy may be edited without having to rewire or
change any hardware.
The need for implementation of Fieldbus in small as well as large systems was considered when
developing the entire 302 series of Fieldbus devices. They have the common features of being able to
act as a master on the network and be configured locally using a magnetic tool, eliminating the need
for a configurator or console in many basic applications.
Some Characteristics:
Input |
0-20
mA, 4-20 mA or any within 0 and 20 mA. Reverse polarity protected. |
Communication |
FOUNDATION
Fieldbus on 31.25 kbit/s voltage
mode according to IEC 61158-2 |
Accuracy |
±0.03%
of span for 4-20 mA, 0.005 mA for other spans |
Power
Supply |
Bus
powered: 9-32 Vdc |
Power
Consumption |
Quiescent
12 mA |
Function
Blocks |
|
Configuration |
Using
local adjustment magnetic tool if device is fitted with LCD display.
Complete configuration possible using PC software interface. |
Indication |
Optional
LCD indicator |
Material |
Injected
low copper aluminum with polyester painting or 316 stainless steel
housing |
Process
Temperature Limits |
-40
to 85 ºC (-40 to 185 ºF) |
Ambient
Humidity Limits |
0
to100 % RH |
Hazardous
Area Certification |
Explosion
proof, weather proof and intrinsically safe |
Mounting |
Wall,
panel, or 2" pipe with optional bracket |
Weight |
Nominal:
0.80 kg;
Digital display adds: 0.13 kg;
Mounting bracket adds: 0.60 kg. |
Library Lists:
Foundation FieldBus
- DD Foundation FieldBus
For download DD, DTM and GSD files of SMAR products, click here.
|