Head Mount Smart Temperature Transmitter 4 to 20 mA + HARTTT421
Head Mount Smart Temperature Transmitter 4 to 20 mA + HART

The Digital Temperature Transmitter TT421 is the cost effective solution for temperature measurement and control dedicated for head mounting.

The Smar TT421 is a powerful and extremely versatile programmable temperature transmitter, which can be used with practically all relevant temperature sensors as well as with load cells, resistance position indicators, etc.

A same unit can be used for different measuring ranges and many types of sensors reducing drastically calibration and maintenance time.

Complete configuration is possible using PC software interface (CONF401) or via Hand-Held (HPC301). Configured to customer specs, prior to shipping.

 

Some Characteristics:

Output Signal
Two-wire, 4-20 mA with HART superimposed digital communication protocol Version 5.1.Output current according to NAMUR-NE43.
Power Supply
12-45 Vdc
Input
Single unit accepts signal from:
  • Thermocouples, RTD's and Differential RTD's
  • mV signals from radiation pyrometers, load cells, etc
  • Ohm signals from position indicators, etc
  • Isolation
    Factory tested isolation for 1500V
    Accuracy
    ± 0.02 % basic accuracy
    Measured Types
    • Single sensor: 2, 3, or 4 wire configurations
    • Dual Sensor

    • - Differential
      - Average
      - Maximum
      - Minimum
    Configuration
    Complete configuration is possible using PC software interface or via Hand-Held
    Calibration
    With applied reference and without reference.
    Access Protection
    Yes, via passwords
    Diagnostics
    Yes, via communication.
    Control Block
    Yes, via PID function.
    Setpoint Generator function
    Yes, ideal for batch processes.
    Alarms
    Dual, trip levels adjustable over entire range.
    High or Low action.
    Acknowledge, messaging
    Linearization
    Linearization international standards and custom calibration according to Callendar Van Dusen
    Temperature Limits
    Ambient: -40 to 75 ºC (-40 to 167 ºF)
    Humidity Limits
    10 to 100% RH
    Mounting
    Mounts in industry standard DIN Form B connection head.