CD600
Digital Controller Multi-Loop
The CD600 is a powerful stand alone single station controller capable of simultaneously controlling up to 4 loops with up to 8 PIDs and more than 120 advanced control blocks.
The CD600 is a microcomputer software for Windows systems which provides users with a user-friendly graphic interface. It can be configured through CD600 Hand-Held Terminal or the CONF600.
- Up to four independent control loops with up to 8 PID functions;
- 8 analog and 4 digital inputs, 8 analog and 8 digital outputs;
- Built-in backup station for both analog and digital outputs;
- 8-digit alphanumeric display and individual buttons for control operations;
- Built-in 24 Vdc 160 mA power supply for up to 8 field transmitters;
- High reliability surface mount technology;
- More than 120 function blocks are available for user's programming;
- Several pre-programmed control configurations including cascade, ratio, feed forward, split range, 3-element boiler feed water control, distillation column control and many more;
- Configuration via microcomputer or Hand-Held Terminal;
- Adjustment of control options through front panel;
Some Characteristics:
| Analog Inputs |
1 to 5 Vdc or 0 to 5 Vdc with input impedance of 1 MΩ
4 to 20 mAdc or 0 to 20 mAdc with 250 Ω shunt resistors (removable) |
| Digital Inputs |
Open Contact: 10 KΩ min or 3 to 24 Vdc
Closed Contact: 200 Ω (maximum) or 0 to 1.7 Vdc maximum 2 inputs may be used for frequency, from 0 to 10 Hz |
| Analog Output |
4-4 to 20 mAdc or 0 to 20 mAdc with maximum load of 750 Ω
4-1 to 5 Vdc or 0 to 5 Vdc with minimum load of 1500 Ω |
| Digital Output |
Transistor open collector, 45 Vdc, 100 mA maximum on resistive load |
| Power Supply |
24 Vdc
110/127/220/240 Vac - 60/50 Hz |
| Auxiliary Power Supply |
24 Vdc, 160 mA maximum for up to 8 field transmitters |
| Indication and Control |
- 101-element LED bargraphs for setpoint and process variable indication
- 41-element LED bargraph for output indication 8-digit
- General purpose alphanumeric display LEDs for alarm, status and loop monitoring
- Function keys
|
| Serial Communication Port |
EIA-485 |
| Configuration Definition |
Software function blocks (programming) or pre-programmed control configurations |
| Configuration Entry |
Hand-held Terminal or IBM-PC compatible |
| Ambient Temperature Limits |
0 to 43 ºC (32 to 109.4 ºF) |
| Ambient Humidity Limits |
20 to 90% RH |
Power Consumption |
Basic: 12.5 VA (ac) / 10 W (dc)
Backup 10 VA (ac) / 8 W (dc)
Add 0.7 VA (ac) or 0.5 W (dc) / transmitter powered |
| Dimensions |
2.834 x 5.669 x 19.468 (in)
72 x 144 x 494 (mm) |
|