RP312-S
Fieldbus Active Repeater
As
cable lengths increase control signals deteriorate and can become unreadable
by devices on the network. Signal repeaters can be used to avoid deterioration
in large networks or over long network cable runs.
The
RP312-S takes an incoming signal from one network segment, "cleans"
it for errors, and re-transmits the signal at full strength to another
network segment, maintaining signal quality and message integrity. throughout
all network segments. The RP312-S performs this function in a bi-directional
fashion to support Fieldbus Networks. It is fully compliant with the
IEC1158-2/ISAS50.02 physical layer definition and specifications for
Foundation Fieldbus and PROFIBUS.
An H1 bus topology Fieldbus network with DC power
can support a network segment cable length of up to 1900 meters. Up
to 4 repeaters may be used in series, providing for the total cable
length of any particular network trunk or spur to be increased up to
5 times the cable length of one segment. This allows for a Fieldbus
device to be located up to 9.5 Km (5.9 miles) away from a control room.
Some Characteristics:
- 1500 VAC Isolation between networks;
- Very Low DC leakage at repeater inputs;
- Each unit can extend the Fieldbus network length up to 1900 meters;
- Provides up to 125 mA at 18 V to the Fieldbus network for field
devices;
- Includes terminators on network side;
- 8 bit preamble can use 4 repeaters; 16 bit preamble can use 8 repeaters
in series;
- Accommodates conductors up to 2.5mm2 (12 AWG);
- Fast snap-on DIN mounting rail assembly;
- Conforms to IEC 61158-2, 31.25 Kbit/s standard for Foundation Fieldbus
and PROFIBUS;